Technical parameters of 12-pulse voltage controlled rectifiers:
Name of parameter | Unit of measurement |
Value |
---|---|---|
Rectification circuit, acc. to IEC 60146-1-1, EN 50328 |
- | № 9 (12-pulse, bridge, 2 bridges in series) |
Rated output voltage | V DC | 1500 * |
Rated output current | A | 2330 ** |
Rated output active power | kW | 3500 *** |
Rated frequency of input voltage | Hz | 50 |
Number of rectifier input voltage phases | 6 | |
Duty class of current load acc. to IEC 60146-1-1, EN 50328 | - | VI ** |
Admissible current loads acc. to IEC 60146-1-1, EN 50328, multiplicity and duration | - | а) 1 – continuous b) 1.5 – within 2 h, after a c) 3 – within 1 min, after a |
Cooling type acc. to IEC 60146-1-1, EN 50328 | - | AN (air, natural) ** |
Auxiliaries network voltage | V | 110 DC / 220 DC, 220 AC / 380 AC / 410 AC |
Coefficient of performance (estimated), min. | % | 0.95 |
Degree of protection acc. to IEC 60529:2013 | - | IP2X |
Thyristors temperature monitoring system | - | 2-level (warning and emergency level) |
Overall dimensions: Width Height Depth (Length) |
mm | 2000 **** 2200 1000 |
* other values of rated output voltage V DC are available for order: 600, 750, 825, 1650, 3000 and 3300
(rectification circuit №12, 12-pulse bridge, 2 bridges are installed in series, is applied for output voltages 3000 V DC и 3300 V DC)
** other values are available upon request
*** is defined by the type of applied converting transformer according to IEC 60146-1-3, EN 50329
**** the width depends on rated output current