Main technical characteristics of PLC-DО-24 output discrete signals module:

Name of Parameter Unit of measurement Value
Number of discrete outputs - 24 (one galvanically isolated group)
Rated output voltage, DC V 24

Output DC, max:
- upon all public keys
- upon 12 public keys of 24 available

mA


50
100

Output overload protection actuation current, DC А 1.4 – 2.0
Output resistance of public key, max. 165 
Private key leakage current, max.  uA 20 per channel
Current of load failure monitoring generator  uA 80 per channel
Maximum output switching frequency kHz 1
Electrical insulation resistance of galvanically isolated circuits (upon test voltage frequency 50 Hz and testing time 1 min.) V 1000
Electrical insulation resistance of galvanically isolated circuits (at U test = 1000 V DС), min. MОhm  100
Module address setting from 0 up to 15 mechanical switching device
Interface of communication with master controller RS-485 (Modbus-RTU Slave up to 115200 bps or CAN (from 50 kHz up to 500 kHz)
Connection/disconnection of matching resistance of connection line 120 Om  - configured with a parameter
Module power supply voltage in +24 V DC circuit 10 – 34
Module power supply voltage in +5 V DC circuit 4.7 – 5.5
Consumption power in +5 V circuit W 0.5
Environmental conditions
Operational temperature °C from -20 up to +45
Storage temperature °C from -40 up to +60
Relative humidity - up to 80 % with no condensed water
Atmospheric pressure kPa from 86 up to 106 (645 – 795 mm Hg)
Operation mode - continuous
Cooling - natural
Type of installation - DIN rail, 35 mm
Protection level EN 60529:2014 - IP 20