PLUTON presents a new SOTA protection and monitoring system More details
Australia |en
Description Unit Value
Rated Voltage kV 27,5
Rated Frequency Hz 50
Rated Current A 630; 1250
Rated Short Time Current 20
Maximum Short-Circuit Current s 3
Rated Peak Withstand Current 50
Rated Impulse Withstand Voltage 170
Rated Withstand Power Frequency Voltage kV 70
Approx. Closing Time ms 65
Arcing Time ms <17
Approx. Opening Time ms 70
Rated Short-Circuit Breaking Current 20
Rated Short-Circuit Making Current 50
Rated Cable Charge Breaking Current A 50
Operating сycles:
- vacuum tube at rated current
- vacuum tube at rated short-circuit breaking current
- circui-breaker mechanism
-  15,000 
100
10,000