General technical characteristics according to IEC 62271-100 |
|||||
Operating voltage — 10(6) kV | Rated breaking current (Isc) | Rated current | |||
Cubicle width (mm) | 650 | 800 | 900 | ||
25 kA | 630 A | + | + | ||
1250 A | + | + | |||
2500 A | + | ||||
31,5 kA | 630 A | + | + | ||
1250 A | + | + | |||
2500 A | + | ||||
Additional characteristics according to IEC 62271-100 | |||||
Rated parameters | |||||
Voltage | Ur | kV | 7,2 | 12 | 12 |
Insulation voltage: - commercial frequency 50 Hz, 1 min - lightning discharge (1,2/50 ms) |
Ud Up |
kV kV |
32 57 |
42 75 |
42 75 |
Frequency | fr | Hz | 50-60 | ||
Short time thermal current | Ik/tk | kA | Isc/3 s | ||
Short time electrodynamic current (surge current) | Ip | kA | 2,5 Isc (50 Hz) | ||
Rated making current | kA | 2,5 Isc (50 Hz) | |||
Other characteristics | |||||
Sequence of operations | O-0.3 s-ВO-15 s-ВO | ||||
O-0.3 s-ВO-3 min-ВO | |||||
O-3 min-ВO-3 min-ВO | |||||
Time response characteristic | Opening | ms | < 50 | ||
Full disconnection | ms | < 60 | |||
Closing | ms | < 71 | |||
Mechanical strength | Class | M2 | |||
Resource cycle | 30 000 | ||||
Switching wear resistance | Class | E2 | |||
Number of switchings at complete Isc value | 25 kA | 100 | |||
31,5 kA | 50 | ||||
Capacitive current breaking capacity | Class | С1 (for certain types) | |||
Operation temperature | –35 °C up to +40 °C | ||||
Average relative humidity | 24 hours | < 95 % | |||
1 month | < 90 % |