PLUTON presents a new SOTA protection and monitoring system More details
Australia |en
Name of parameter Unit of measurement Value
Rated voltage kV 6 10
Maximum operating voltage kV 7.2 12
Power frequency withstand voltage 50 Hz during 1 min  kV 32 42
Pulse value 1.2/50 mks kV 60 75
Thermal resistance current kА/3 s 25 
31,5
Electrodynamical resistance current 62,5 
81
Busbars rated current A  1250 
2500
Main circuits rated current A  630 
1250
2500
Internal arc resistance (option)   
IAC-AFLR kA/0.5 s 25