PLUTON presents a new SOTA protection and monitoring system More details
Australia |en
Parameter group Parameter name Value
Network connection Network voltage Uin 208…240 V; 380…500 V; 525…690 V; - 10 %...+10 %
Network frequency 45…66 Hz
Network connection One per minute or more rarely (normal mode)
Motor connection Output voltage 0 — Uin
      Continuous output current      IH: maximum ambient temperature
     +50 °C, overload 1.5 x IH (1 min/10 min)
IL: maximum ambient temperature
     +40 °C, overload 1.1 x IL (1 min/10 min)
Starting moment Is within 2 s, depends on motor torque
Starting current Is 2 s each 20 s
Output frequency 0…320 Hz (NXS); 7200 Hz (special application)
Frequency resolution 0.01 Hz (NXS); depends on used application (NXP)
Control characteristics  Control method U/f frequency control
Vector control with open-loop feedback
U/f control with closed-loop feedback
Vector control with closed-loop feedback (only NXP)
Switching frequency
(See parameter 2.6.9)
For drives up to NX_0061 inclusively:
1…16 kHz; Factory setting 10 kHz
For drives from NX_0072: 1…10 kHz; Factory setting 3.6 kHz.
Frequency setting:
Analogue input
Control panel
Resolution 0,1 % (10-bit), accuracy ±1 %
Resolution 0,01 Hz
Field reduction point 30…320 Hz
Acceleration time 0…3000 s
Deceleration time 0…3000 s
Braking moment DC braking: 30 % * TN (without dynamic breaking unit)
Electromagnetic compatibility (default setting) Interference resistance Meets all standards requirements
Interference emission Electromagnetic compatibility level H: EN 61800-3 (1996)+A11 (2000) (1st environment, restricted distribution); EN 61000-6-4 Electromagnetic compatibility level L: EN 61800-3 (1996)+A11 (2000) (2nd environment)
Safety - EN 50178 (1997), EN 60204-1 (1996), EN 60950 (2000,3rd edition) (as basic), CE, UL, CUL, FI, GOST R, IEC 61800-5; (For additional information see nameplate)
Control circuits Analogue input 0…+10 V , Ri = 200 k­, (–10 V…+10 V joystick control) 
resolution 0.1%, accuracy ±1%
Analogue input (current) 0 (4)…20 mA, Ri = 250­ differential
Discrete inputs (6) Positive or negative logic; 18…30 V DC
Auxiliary voltage +24 V , ±15 %, max. 250 mA
Reference voltage +10 V, +3 %, max. load 10 mA
Analogue output 0(4)…20 mA; RL max. 500­; Resolution 10 bit; Accuracy ±2 %
Discrete outputs Open-collector transistor, 50 mA/48 V
Relay outputs 2 freely-programmable relay outputs
- Switching capacity: 24 V DC/8 A, 250 V AC/8 A,
125 V DC/0,4 A. min. switchable load: 5 V /10 mA
Protection functions Overcurrent protection Tripping limit 4.0*IH
Overvoltage protection
Undervoltage protection
NX_2: 437 V DC; NX_5: 911 V DC; NX_6: 1200 V DC 
NX_2: 183 V DC; NX_5: 333 V DC; NX_6: 460 V DC
Earth fault protection In case of earth fault or in motor cable, 
only frequency converter protects itself
Supply network phases control Tripping in case of any supply network phase loss
Output network phases control Tripping in case of any output circuit phase loss
Against converter overheating Available
Against motor overload Available
Against motor seizure Available
Against underload operation Available
Against short circuits in +24 V and +10 V circuits Available
Casing class IР 20, IP 00, IР 21, IP 54